Effect of Magnetic Treatment on Circulating Water

姜丽丽,左海滨,张建良,杨天钧,谭赞麟
DOI: https://doi.org/10.13228/j.boyuan.issn1001-0963.2009.10.001
2009-01-01
Abstract:At present the methods used are chemical treatment methods, which can cause secondary pollution or spend a lot of money, in order to prevent the emergence of cooling water pipe corrosion and scaling issues, the physical method such as magnetic treatment is used to test the effect of different magnetic intensity, the treatment time and the flow rate on the parameters such as PSI, pH and the electrical conductivity. The results show that the optimum magnetic intensity is 34 000 Gs and the lower pH value can be obtained, so that old scale falls off,and the possibility of scale formation is reduced. The cooling water of blast furnace in Shougang is magnetically treated and good results are obtained.
What problem does this paper attempt to address?