Abstract:The control of the temperature of superheated steam is complex due to the large inertia and resulting lag times. Thus, the dynamic behavior of steam temperature controllers vary widely depending on the operating conditions. This paper presents a multi-model internal mode control strategy that has been successfully applied to a 1 024 t/h super-critical pressure boiler. Five linear models were developed based on the unit's operating range with associated controllers. Performance studies show that the control strategy ensures that the superheated steam temperature stays within the desired range for both steady and varying loads.