Numerical Simulation and Linear Heat Source Integrated Model of Vertical Embedded Pipe for Ground Source Heat Pump

LU Zhi,LIAN Zhi-wei,LIU Wei-wei,LAN Li
DOI: https://doi.org/10.3321/j.issn:1006-2467.2008.03.012
2008-01-01
Abstract:In order to simulate swiftly about the heat transfer under ground with enough high precision,a numerical and linear heat source integrated model(NLIM) was developed by analyzing the unsteady heat transfer of vertical embedded pipe for ground source heat pump,and integrating the merits of the numerical simulation method and finite-length linear heat source model.This model was validated by comparing the simulation results with experimental data given in published papers.Compared with the similar models,it need not to calculate iteratively to get the ground temperature out of replaceable radius,and can simulate quickly the temperature response underground after a long period running of a ground source heat pump system with enough high precision.Especially,this model can even more quickly simulate the ground temperature after heat pumps being turned off for a long time during transitional season.And also,the value of replaceable radius in linear heat source model were given.
What problem does this paper attempt to address?