Influences of Secondary Air on Erosion in Rectangular Circulating Fluidized Bed Boiler

马志刚,方梦祥,王勤辉,骆仲泱,岑可法
DOI: https://doi.org/10.3321/j.issn:1006-8740.2008.03.007
2008-01-01
Abstract:After numerical simulation validity was confirmed by experimental results on cold model test,the erosion property in a circulating fluidized bed(CFB) with a rectangular cross-section was analyzed using numerical simulation under the condition of different primary/secondary air ratio,different up/down secondary air ratio and different front/back secondary air ratio.The results show that high secondary air ratio will reduce erosion of boiler.Erosion shows no obvious change with the up/down secondary air ratio.Besides, high proportion front wall secondary air will accelerate the gas solid flow toward the outlet resulting in the increase of erosion in CFB boiler.In order to reduce erosion,it is necessary to increase the proportion of secondary air.At the same time,it is important to control appropriate rate of secondary air to avoid cut-off effect on uprising fluid.The ratio of front wall secondary air to back wall secondary air is recommended adopt 50/50.Furthermore,furnace corner protection of rectangular CFB is also needed,and it is helpful to adopt rounding off in projection section and to reduce irregular region.The design of outlet has an influence on erosion of dilute region,and as for this boiler,the anti-attrition measures should be taken to reduce erosion of back and left walls of the dilute region.