Chlorine wall decay coefficients calibration of water distribution quality model

Tu-qiao ZHANG,Hong-xiang WANG,Shuai GUO
DOI: https://doi.org/10.3785/j.issn.1008-973X.2008.11.025
2008-01-01
Abstract:Chlorine wall decay coefficients vary between pipes and can be determined indirectly from field measured concentration data. A general calibration model under multi-mode to identify these parameters was formulated based on the simple first-order reaction of chlorine and the Lagrangian time-based approach of dynamic water quality model. The multi-mode model was analyzed to collect more node residual chlorine data for calibration. Max-min ant colony system algorithm was proposed to solve the calibration model that was coupled with hydraulic and water quality simulation models using EPANET2 Toolkits. Only elitist ant was allowed to provide feedback mechanism by updating the trails and the trails were limited to an interval between some maximum and minimum possible values. Empirical coefficients were utilized corresponding with local heuristic function to improve the convergence of optimization. Case study showed that the chlorine wall decay coefficients calibrated by the max-min ant colony system algorithm gave perfect match between the actual and computed node residual chlorine values.