PERFORMANCE COMPARISON OF ENERGY RECOVERY VENTILATOR WITH DIFFERENT INDOOR AND OUTDOOR AIR PARAMETERS

Yanping Zhou,Jingyi Wu,Ruzhu Wang
DOI: https://doi.org/10.3321/j.issn:0254-0096.2008.02.014
2008-01-01
Abstract:The simulation model of energy recovery ventilator (ERV) was built and validated experimentally, and the sensible heat and latent heat recovery of ERV as well as the operating efficiency were investigated both for Beijing and Shanghai weathers with different temperature set-points. Simulation results show that the maximum value of sensible and latent heat recovery in winter is ten times as much as the counterpart in transitional and summer season in Beijing, while five times in Shanghai. The energy recovery in transitional and summer season is tiny against that in winter. The Beijing annually average sensible and latent heat efficiencies are larger than those in Shanghai. The weather has minor impact on the performance of ERV with the differences of sensible and latent heat efficiencies in 3.1% and 4.3% for various weathers, respectively. The sensible and latent heat efficiencies for both cities appear show concave in a year scale, whilst the value for sensible efficiency in August, or the value for latent heat efficiency in May reach the yearly lowest point.