Performance of Energy Recovery Ventilator with Various Weathers and Temperature Set-Points

Y. P. Zhou,J. Y. Wu,R. Z. Wang
DOI: https://doi.org/10.1016/j.enbuild.2006.12.010
IF: 7.201
2007-01-01
Energy and Buildings
Abstract:Based on the generic dynamic building energy simulation environment, EnergyPlus, the simulation model of energy recovery ventilator (ERV) is developed in this paper. With different indoor temperature set-points, the energy performance of ERV along with the availability of ERV is investigated both for Beijing and Shanghai weathers in China in terms of the ratio of heat recovery to energy supply by HVAC devices and ERV. Simulation results show that the seasonal average of the ratio is linear with indoor temperature set-points. The availability of ERV in Shanghai is better than that in Beijing during the winter. In summer, the utilization of ERV is uneconomical if the indoor temperature set-point is higher than 24°C for the Beijing climate. The indoor temperature set-points have the reverse effects to the availability of ERV in the mid-season and to that in the hottest months. Meanwhile, the heating amount recovery in summer and the cooling amount recovery in winter, both of which impair the strong points of the energy recovery, are analyzed quantitatively.