Correlation analysis for faulty feeder detection in resonant earthed system

Hongchun SHU,Liang XU,Shixin PENG,Xiangfei SUN
DOI: https://doi.org/10.3969/j.issn.1006-6047.2008.09.002
2008-01-01
Abstract:The zero modulus current asymmetric components of faulty line are very similar to those of healthy line in resonant earthed system before incident, which strongly influences their correlation coefficient. The pure fault component of zero modulus current can be obtained by subtracting the sampled data of the first cycle zero modulus current before fault from those of the first cycle zero modulus current after fault. A faulty line detection method based on the correlation analysis is proposed, which analyzes under certain data window the integrated correlation coefficient of pure fault component of zero modulus current for each feeder and takes the line with the smallest one as the faulty line. Theoretical analysis and simulative results show that, the proposed method is accurate and reliable, with the enhanced protection margin and the excellent performance in arc earthing detection and asymmetric component impact suppression.