Transient characteristics of Rogowski coil-based current sensor

Wei LI,Xianggen YIN,Deshu CHEN,Wei CHEN,Zhe ZHANG,Yixiong NIE,Xiaotao HAN,Bin XIE
DOI: https://doi.org/10.3969/j.issn.1006-6047.2008.10.007
2008-01-01
Abstract:To improve the transient characteristics of ECT (Electronic Current Transducer) based on Rogowski coil, the transient characteristics simulation of Rogowski coil with ideal integrator and actual integrator is carried out. Simulation results show that the ECT transient performance is excellent when ideal integrator is used, while it is greatly degraded when improperly designed non-ideal integrator is used. Increase of the integrator resistor or capacitor will improve the ECT transient performance. Simulative analysis is carried out for comparison, in which the strictest decay time constant of transient current is taken according to IEC60044-8 and different integrator parameters are selected. A set of proper non-ideal integrator parameters is thus determined, based on it, an ECT composed of Rogowski coil and improved non-ideal integrator is designed. Experiments show it has high static AC measuring precision and perfect performance in transient fault current measuring.
What problem does this paper attempt to address?