Analysis of Grounding Modes of 110 Kv Side of Transformer in 220 Kv Substation

HUANG Fang-neng,HUANG Cheng-jun,JIANG Xiu-chen,ZENG Yi,WANG Heng,WANG Xin-tong
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.12.036
2007-01-01
Abstract:The grounding modes of main transformer in 220 kV transformer station will influence the stability of main transformers significantly. Short circuit current may do harm to transformer when a single-phase grounding fault occurs in the 110 kV side of 220 kV Transformer Substation.Main transformers in 220 kV transformer station are three-winding transformer commonly,their winding structures are usually Y/y/d connected with the neutrals grounded modes.This paper presents the possible grounding modes of 220 kV transformer substation,and analyses the influence of grounding modes of 220 kV Transformer Substation on the short circuit current that feeds into transformer when a single phase grounding occurs in the 110 kV side of 220 kV transformer substation,the method for computing the short circuit current is also provided.The single-phase grounding is the worst fault that does harm to transformer,and transformer could be protected by selecting suitable grounding modes.The main transformer neutral grounding via little reactance will enlarge the zero sequence equivalent reactance of electric power system,meanwhile,single phase shorts circuit current will remarkably reduce and the shorts circuit currents that feed into the winding of transformer will reduce too,this method could protect main transformers in 220kV transformer substation effectively.At the end,an actual case of Tangshan electric power company was presented.