Measurement and Frequency Analysis of Short Current and Its Ground Wire Shunting at Artificial Grounding Fault on AC and DC Transmission Lines
Yutang MA,Caowei HUANG,Ke WANG,Bo ZHANG,Jinliang HE,Fangrong ZHOU
DOI: https://doi.org/10.13336/j.1003-6520.hve.20171127013
2017-01-01
Abstract:Grounding short-circuit fault is a common fault for AC and DC transmission lines.The shunting of the short-circuit current in the ground wires and the frequency components of the short-circuit current are very important for analyzing the influences of the short-circuit current on the pipelines and other facilities near the transmission lines.Con-sequently,on the basis of the first ±500 kV HVDC transmission project in Yunnan Province,we artificially and experimentally investigated the grounding short-circuit on AC and DC transmission lines.The shunting of the short-circuit current was measured in the substation outlet or the middle of the transmission line depending on the position and the type of the fault.Moreover,the features of the current shunting and frequency components of the fault current were analyzed.The main conclusions are drawn as follows:AC short-circuit current decays with oscillation,and the frequency components consisting of 50 Hz is dominant,being accompanied with DC component with frequencies higher than 50 Hz.DC short-circuit current is a simple waveform without oscillation,which increases initially and then decreases.The main frequency component is below 30 Hz,which is related to the DC system blocking time.The frequency components also include a small amount of 50 Hz,160 Hz,340 Hz,and 1 800 Hz.According to all the tests,no matter short-circuit current takes place in the substation outlet or the middle of the transmission line,more than 60% of the short-circuit current flows away from the ground wires,which is consistent with the simulation result.