Primary design and protection of 110kV substation

X J Feng,Y Q Chen
DOI: https://doi.org/10.1088/1755-1315/267/4/042015
2019-05-01
IOP Conference Series: Earth and Environmental Science
Abstract:Abstract This paper designs a 110KV substation. Through the analysis of transformer load, the capacity and number of main transformers are selected, and the main connection modes of 110kV, 35kV and 10kV are determined. By calculating the short-circuit current, it can be used to select the main electrical equipment to complete the design of transformer protection and the selection of distribution devices, and draw the main wiring diagram and the plane layout. Finally, we design a simple relay protection, and complete the design of the primary electrical part of 110kV substation.
What problem does this paper attempt to address?
This paper aims to design an 110 - kV substation and solve the design and protection problems of its main electrical parts. Specifically, by analyzing the transformer load, the paper selects the capacity and quantity of the main transformer and determines the main connection modes of 110kV, 35kV and 10kV. By calculating the short - circuit current, it is used to select the main electrical equipment, complete the selection of transformer protection and power distribution devices, and draw the main wiring diagram and plane layout. Finally, a simple relay protection system is designed, and the design of the primary electrical part of the 110 - kV substation is completed. The key steps mentioned in the paper include: 1. **Design Principles of Main Electrical Wiring**: Discusses the selection of wiring modes under different voltage levels, such as bridge connection, single - busbar, double - busbar, etc., and the setting principles of circuit breakers. 2. **Load Calculation and Determination of Main Transformer Capacity**: Uses the maximum load calculation formula: \[ S_{max} = K_t \left(\sum_{i = 1}^{n}\frac{P_{i,max}}{\cos\phi_n}\right)(1+\alpha\%) \] to calculate the loads of each voltage level and determine the capacity of the main transformer. 3. **Short - Circuit Current Calculation**: Uses the short - circuit impact current calculation formula: \[ i_{sh}=\sqrt{2}I_p(1 + e^{- 0.01\theta_{ta}})=\sqrt{2}K_{sh}I_p \] to calculate the short - circuit currents of each voltage level. 4. **Selection of Parallel Capacitor Capacity**: According to the reactive power calculation formula required by the load: \[ Q_c=\frac{P_m}{\tan\phi_m-\tan\phi_l} \] selects the appropriate capacitor bank and its parameters. 5. **Transformer Protection Configuration**: Designs the main protection measures for the transformer, including longitudinal differential protection and gas protection, as well as other non - electrical protection devices. Through these steps, the paper elaborates in detail how to design and protect an 110 - kV substation to ensure its economic, reasonable, safe and reliable operation.