Review and Expectation of Diagnosis Technology on Insulation of DC Cable of Urban Transit

Xiaojun Shen,Xiuchen Jiang,Shipeng Da
DOI: https://doi.org/10.3321/j.issn:1000-6753.2007.09.005
2007-01-01
Abstract:Because of its bad laying environment, the insulation of direct current (DC) feeder cable is a serious hidden trouble factor threatened the operation safety of urban transit. This paper reviews the current diagnosis technology on the insulation of DC cable of urban transit and expects its development. The results of analysis indicate that the implemented diagnosis technology, off-line periodic testing and motion alarming of kinds of protection, didn’t meet the demand of safety operation of urban transit; therefore the new fault predicting technology shall be developed. But at present the on-line monitoring technology is concentrated on AC cable, the relevant research on DC feeder cable is scarcely carried out around the world, so the paper investigates the feasibility of using the on-line monitoring technology on AC cable to detect the DC feeder cable. The results of study show that the on-line monitoring technology on AC cable can not be adopted, but the discharge method and DC leakage current method can be used for reference, and the relevant technology should be investigated in times in order to enhance the safety of power supply of urban transit.
What problem does this paper attempt to address?