HVDC Transmission System Fault Identification and Locating Algorithm Using Mathematical Morphology

SHU Hong-chun,WANG Chao,ZHANG Jie,WU Na
DOI: https://doi.org/10.3969/j.issn.1006-6047.2007.04.002
2007-01-01
Abstract:Effective fault traveling wavefront identification and fault locating method is the basis of traveling wave protection.The principle and algorithm of mathematical morphology are introduced,based on which the amplitude and polarity of the refractive and reflected transient traveling waves are abstracted by transient fault voltage traveling wave treatment using MMG(Multi-resolution Mor-phological Gradient) method and the HVDC(High Voltage DC transmission) line faults identified and located using single and double ending fault locating methods.Some types of HVDC faults similar to line fault transient are discussed,such as commutation failure and AC single-phase grounding fault near inverter station.Simulations with Matlab show that the proposed criterion and algorithm work well in distinguishing HVDC line fault and some other similar faults,and correct locating the fault position.