A Study of Zero Reference Effects on Electromagnetic Transientient Measurements of a Grounding Electrode

M. Nayel,J. Zhao,A. Ametani,J. He,Z. Cai,Q. Wang
DOI: https://doi.org/10.1109/isemc.2006.1706318
2006-01-01
Abstract:This paper presents the effect of zero reference used in measurements of a grounding electrode transient characteristics. Experimental measurements of many cases of Zero reference have been carried out. Different lengths (20 m, 40 m and 60 m) of the zero reference wire in same and right angel directions to the lead wire direction are examined to obtain their effects on transient voltages of the grounding electrode. Zero reference wire is replaced by a cable with different sheath ends grounding in same and right angel directions. Open end and grounded end of zero reference for different cases are tested and studied. The results show that as the length of zero reference wire increases the measured results accuracy increases. Replace zero reference wire by the cable of grounded sheath at both terminals results to the most accurate measurements.