Fault Detection and Diagnosis for AHU Sensors with Fixed or Drift Bias

DU Zhi-min,JIN Xin-qiao,WU Li-zhou,CHEN Dan-dan
DOI: https://doi.org/10.3969/j.issn.1004-731x.2006.06.061
2006-01-01
Abstract:A statistic method combining principal component analysis(PCA)with joint angle plot was proposed to online detect and diagnose fixed or drift bias of temperature and flow rate sensors of air handling unit(AHU).PCA model was set up based on the normal history data of the system to detect the sensor faults by comparing the projection on the residual subspace to which the real measurement vector and normal vector were projected.Whereas,the joint angle method,which could improve the Q-statistic plots method,was used to isolate the fault source on line employing the history fault knowledge.