Fault Detection and Diagnosis Based on Improved PCA with JAA Method in VAV Systems

Zhimin Du,Xinqiao Jin,Lizhou Wu
DOI: https://doi.org/10.1016/j.buildenv.2006.08.011
IF: 7.093
2007-01-01
Building and Environment
Abstract:In this paper, improved principal component analysis (PCA) with joint angle analysis (JAA) is presented to detect and diagnose both fixed and drifting biases of sensors in variable air volume (VAV) systems. Fault characteristic concerned in PID controller in the VAV systems is analyzed and discussed. The squared prediction error (SPE) plot based on PCA is used to detect the sensor fixed and drifting biases. Then the JAA plot instead of conventional contribution plot is used to diagnose the faults. And they are tested and evaluated online in a simulated centralized VAV air-conditioning systems.
What problem does this paper attempt to address?