Thermodynamic Analysis on Cascade Refrigeration System with CO2 Working in Low Temperature Stage

卢苇,马一太,王志国,李敏霞
DOI: https://doi.org/10.3969/j.issn.0493-2137.2004.03.013
2004-01-01
Abstract:Some refrigerants used in traditional cascade refigerating system can destruct the ozonesphere and cause strong greenhouse effect,so the cascade refrigeration systems with CO_2 working in the low temperature stage are analysed theoretically in this paper. The variation of optimum coefficient of performance (COP) was calculated with the change of the evaporation temperature.The condensation temperature for the low temperature stage and mass flow ratio for the high temperature stage to that of the low temperature corresponding to the optimum COP of different evaporation temperature was also calculated . Comparisons between several groups of refrigerant combinations (R22-R12, R134a-CO_2, NH_3-CO_2, R290-CO_2, CO_2-CO_2, and CO_2-CO_2 with expander), show that the COPs of natural working fluids are quite the same as those of conventional ones. Therefore, the natural working fluids systems are promising if the environmental factors and the selection of equipment are taken into account comprehensively.