Discussion on Start-up Mode of LiBr Absorption Chiller

王磊,陆震
DOI: https://doi.org/10.3321/j.issn:1006-2467.2004.02.032
2004-01-01
Shanghai Jiaotong Daxue Xuebao/Journal of Shanghai Jiaotong University
Abstract:In order to reduce the running time and the energy consumption, the dynamic performance of LiBr absorption chiller under different start-up mode was investigated by experiment. The result indicates that the moment to start producing the cooling capacity is related to the moment of turning on the refrigerant spraying pump; the sequence and the moment of turning on the burner and the solution circulating pump have great effect on the dynamic performance of start up process. The different start-up mode can be used for the absorption chiller with different size of the high-and low-pressure generator and the mount of the solution in their drum.