Effects of solution heat exchanger on the performance of absorption chiller

Wan Zhongmin,Wang Xiaoming,Shu Shuiming,Fan Aiwu
DOI: https://doi.org/10.3969/j.issn.1009-8402.2007.04.007
2007-01-01
Abstract:Establishes the simulation model of solution heat exchanger of two-stage absorption refrigeration cycle.Analyzes the effects of strong LiBr solution temperature difference between inlet and outlet of solution heat exchanger on the coefficient of performance(COP) and cooling water flowrate of two-absorption refrigeration cycle,at the same time,the effects of temperature difference on the unit heat exchange area of counterfolw and crossflow solution heat exchangers.The theoretical analysis result shows that there is a optimal value for the strong LiBr solution temperature difference,for the two-stage absorption system,the optimal temperature difference is about 13 ℃,the coresponding COP is 12.3% higher than that of system without heat exchanger,the cooling water flow rate is 8.8% less than that of system without heat exchanger.The optimal temperature difference is helpful for decreasing the volume of solution heat exchanger and improving economic characteristic and system performance.