Algorithm for Quickly Calculating the Pollutant Distribution in Central Ventilation Systems

杨建荣,李先庭,孟彬彬,赵彬
DOI: https://doi.org/10.3321/j.issn:1000-0054.2004.06.015
2004-01-01
Abstract:A calculation model was developed to calculate the value of a new index for quickly and accurately evaluating the indoor air quality in central ventilation systems. The contaminant accessibility index first describes the non-uniformity of the indoor contaminant distribution when the system supplies all fresh air. Then the model was used to calculate the final pollutant distribution in a real system with air re-circulation and local exhaust including the impact of source location, air re-circulation and local exhaust on the indoor pollutants. The conventional lumped parameter method was used to determine the boundary conditions for the computational fluid dynamics (CFD) model. The model can predict indoor concentration after only one CFD calculation for each room in the system. The results show that the model gives more accurate results than the lumped parameter method and greatly reduces the number of iterations required of the CFD simulation.