Optimal study of the energy-saving on vertical laminar flow clean room

Zhihua Zhou,Guangbeu Tu,SongBo Yu
2003-01-01
Abstract:It is obvious that some methods like local clean room, parallel clean tunnel have been widely used as an energy-saving measure in order to reduce the clean area on the working level. However, some projects need relatively high cleanliness, such as class 100, in the whole room. The object of this thesis is to find out whether we can gain a required degree of cleanliness under the condition of low air supply area ratio and low air exchange number. So, we use CFD to analyze velocity, contamination field and airflow field under several conditions. Then we compare the results of numerical treatment and testing in clean room. As a result, we conclude that under a suitable condition, the vertical "laminar" flow clean room can also have relatively high cleanliness without full HEPA in the ceiling frame.