APPLICATION OF ON-LOAD CURRENT METHOD IN MONITORING THE CONDITION OF TRANSFORMER'S CORE BASED ON THE VIBRATION ANALYSIS METHOD

汲胜昌,李彦明,傅晨钊
DOI: https://doi.org/10.3321/j.issn:0258-8013.2003.06.030
2003-01-01
Abstract:The vibration method is an effective method used for on-line monitoring the power transformer' delitescent fault, it can monitor not only the winding, but also the condition of core. In this paper, a method extracting core's vibration signal with operating transformer at on-load condition was introduced. The transformer's vibration accelerated signals at different on-load current and no-load condition were measured. From the fitted curve of on-load current versus fundamental frequency component of vibration accelerated signal, the value of fundamental frequency component was gained as the on-load current was zero, and it was almost equivalent to the fundamental frequency component of vibration accelerated signal measured at no-load condition, thus using on-load current method the fundamental frequency component of core's vibration can be acquired. The core with fault was finally monitored using the on-load current method compared with WPT method. From the result of experiment, we can see this method is very useful to estimate the condition of the transformer' core.