Measurement and Conversion of Four-Way Reversing Valve Capacity in Heat Pump System

Zhen-ming XUE,Guo-liang DING,Zhi-jiu CHEN
DOI: https://doi.org/10.3321/j.issn:1006-2467.2000.09.007
2000-01-01
Shanghai Jiaotong Daxue Xuebao/Journal of Shanghai Jiaotong University
Abstract:As an important component of a heat pump, four-way reversing valve is chosen mainly according to its capacity. Now in industry, its capacity is determined by experiments with air as the working fluid. This method is simple but the measurement result is fairly larger than the real value. In order to revise that difference, this paper analyzes the testing theory and found that the capacity difference is caused by the fact that the refrigerant in four-way reversing valve is generally near the saturation point, and its physical characteristics will affect the flow. With the introduction of the medium revision factor according to the heat expansion coefficient used in the flow measurement instruments, the conversion formula from the air test value to the real capacity is given.