Research on precision of method to measure performance of aircooled heat pump at site based on energy conservation of compressor

Wenyu HUANG,Lianrui DING,Baolong WANG,Wenxing SHI
2016-01-01
Abstract:In order to figure out the field performance of air-source heat pump, a method of measuring the flow rate of refrigerant based on the energy conservation of compressor is proposed, the precision of this method is verified in the standard environment of laboratory, results indicate that the maximum relative error is 6.8% with pressure sensors and temperature sensors and 8.6% with all temperature sensors. Moreover, the relative error comes to 8.36% and 10.12% while in the field test. The experiment result show that the method of measuring the flow rate of refrigerant to obtain the field performance of the unit has a good adaptability in the test of air-cooled water chiller, so that it can be applied as a way to ensure the accuracy of the field test, at the same time, provides the possibility to measuring the field performance for the air to air heat pump like household air-conditioners.