Operation and control of ASVG under asymmetric system conditions

Qirong Jiang,Dong Shen,Yingdu Han,Xiang Li,ZunYi Liu,Yong Ji
1997-01-01
Abstract:An approach controlling the triggering pulse of GTOs of the advanced static var generator (ASVG) to generate a negative sequence voltage component while generating positive sequence voltage to counteract the system negative sequence component in order to suppress the negative sequence current through ASVG caused by system negative sequence voltage is presented. An algorithm to control the triggering pulse of ASVG is proposed based on modelling ASVG with the function of switching method. ASVG can operate normally and not overcurrent under a 15% negative sequence voltage component in the system voltage with this control algorithm. Simulation results show that the analysis and algorithm are correct.
What problem does this paper attempt to address?