Influence of voltage unbalance on the advanced static var generator

Li Zhang,Jianye Chen,Zhonghong Wang,Yingduo Han,Qingxiang X. Zhu,Feng Lin,Xiwen Wang
1997-01-01
Abstract:The influence of the system voltage unbalance on the advanced static var generator (ASVG) has been discussed through the ways of theoretical analysis and simulation. It is recognized that the DC capacitor voltage pulsation and negative sequence current, which is caused by the power flow due to the system negative sequence voltage, is the key point that influences the operation of ASVG. Larger system voltage unbalance degree causes larger capacitor voltage pulsation and negative sequence current. Using the following control method such as choosing the positive sequence voltage as the synchronizing signal of ASVG output voltage, using a larger capacitor C, reactance L, and using a 100Hz LC resonant filter can restrain the influence of the system voltage unbalance effectively.
What problem does this paper attempt to address?