Wave Process Simulation Analysis of 1100 kV GIS Under Oscillation Impulse Testing Voltages
Jun KANG,Qiuyang LI,Yuan LI,Quanlei QU,Jiangtao LI,Mengchen HU,Peng CHENG,Jie PENG,Yujie WANG
DOI: https://doi.org/10.13296/j.1001-1609.hva.2018.02.004
2018-01-01
Abstract:In the process of field impulse voltage withstand test of UHV GIS(gas insulated switchgear),electromagnetic waves in GIS affected by oscillatory surge voltage are prone to refraction and reflection,and that will causes the voltage waves superposition may higher than the test voltage required by the standard,endangering GIS insulation.To effectively evaluate the GIS overvohage in case of oscillatory surge,the impulse voltage test method is optimized.The voltage distribution of each GIS node of is obtained by utilizing EMTP simulation software,based on field test parameters,for the simulation of and analysis on the wave process in two different conditions,normal impulse withstand voltage of GIS and flashover of GIS in the test process.The results show that GIS nodes demonstrated similar voltage without noticeable wave process in case of normal oscillatory surge of GIS.However,in case of internal flashover,the end node voltage of GIS branch affected by the cut-off voltage waves would greatly exceed the test voltage,triggering secondary flashover.In consideration of this case,feasible suppression measures are proposed on the basis of simulation calculation and in combination with actual conditions,which provides a technical basis for the field impulse voltage test of 1 100 kV GIS equipment in the future.