Impact of Wind Farm Integration on Relay Protection(7):Analysis of Relay Protection Configuration for Wind Farm Outgoing Power Grid

ZHANG Baohui,YUAN Bo,WANG Jin,WANG Xiaoli,HUANG Renmou,WU Weiming
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.07.001
2013-01-01
Abstract:The RTDS experiment is carried out for the relay protections of outgoing power grid of largescale grid-connected wind farm and its existing problems are pointed out.The corresponding suggestions about the relay configuration are proposed:the main protection of 110 kV outgoing transmission line should adopt the phase-split current differential protection while its backup protection adopt the distance section I using differential equation algorithm,or the time setting of phasor-based distance section Ⅰ be prolonged by 0.15 s while the conventional distance section Ⅱ,distance section Ⅲ and zero-sequence current protection be equipped;the main protection of outgoing transformer should adopt the differential protection with the inrush current criterion using the dead angle identification,time-difference method,etc.while its backup protection adopt the compound over-current protection and zero-sequence current direction protection;the main protection of 330 kV outgoing transmission line should adopt two independent sets of phase-split current differential protection with the voltage sudden-change phase selector and zero-sequence directional component while its backup protection adopt the same configuration as that of 110 kV outgoing transmission line.