Influence of DC voltage on creepage flashover of oil-paper insulation under composite AC and DC voltage

Yanchao Sha,Yuanxiang Zhou,Qinghua Sun,Meng Huang,Fubao Jin,Jianwen Huang
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.06.008
2013-01-01
Abstract:For further understanding creepage flashover in converter transformers, we studied the creepage flashover under oil-paper insulation of two electrode structures which were in the presence and absence of the back electrode, and adopted a power supply for composite AC and DC voltage to provide an adjustable percentage of DC voltage. The results showed that the flashover voltage in the presence of the back electrode was lower than that in the absence of the back electrode. Furthermore, for both electrode structures, there was the lowest flashover voltage under pure AC voltage, and the flashover voltage increased with DC component of the composite voltage. Besides, to find out the effect of interface of oil-paper insulation, flashover voltages of pure oil under the same electrode structures were also studied. The breakdown voltage of pure oil was compared with that of oil-paper insulation. The comparison showed that, when DC component was relatively low, the breakdown voltage was decreased by the interface of oil-paper, yet it would be increased by the interface if the DC voltage component was large enough. From composite AC and DC electric field point of view, when DC component was low, there would be larger electric filed around the electrode, leading to the oil molecules ionizing that produced a large amount of current carriers, and then promoted the development of creepage flashover. However, with the increase of DC component, the electric field distribution would change and the creepage flashover voltage would increase. At the same time, the electric field distribution mentioned above also caused the fact that the flashover voltage was lower than breakdown voltage when DC component was relatively low.
What problem does this paper attempt to address?