FAULT-TOLERANT THREE-PHASE FOUR SWITCH GRID-CONNECTED INVERTER BASED ON SLIDING MODE CONTROL

Shiying Hou,Xing Song,Tao Sun,Chuang Zhang
DOI: https://doi.org/10.3969/j.issn.0254-0096.2013.02.011
2013-01-01
Abstract:The three phase four switch grid-connected inverter can be used as a reconfiguration topology of traditional three-phase bridge grid-connected inverter after some fault modes were tolerated, three phase four switch grid-connected inverter is worthwhile to study. Based on the principle analysis of the fault-tolerant three-phase four switch grid-connected inverter, its sliding mode control (SMC) was researched. SMC has good dynamic and static performance and ensures that the three-phase four switch grid-connected inverter can transmit high quality electrical energy to grid and obtain good dynamic performance and static performance in fault-tolerant operation mode. Finally, four sections operation mode of three-phase four switch grid-connected inverter was analyzed to make only one switch tube work for each phase in each section of the corresponding interval, which can reduce the probability of bridge arm break-though problem. The simulation results show that the three phase four switch grid-connected inverter with SMC has good inhibitory ability to input disturbances and the grid voltage disturbance. It shows good dynamic and static performance, and output grid current waveform harmonic content is low, waveform quality is good. So it can still transmit high quality electrical energy to grid in fault-tolerant operation mode.