Experimental Study of Ultrasound Atomization Dehumidifying System with Liquid Desiccant

边争,连之伟
2012-01-01
Abstract:The dehumidification efficiency of the ultrasound atomization dehumidifying system with liquid desiccant was studied experimentally.The effects of quality concentration of calcium chloride and lithium chloride mixture solution,liquid-air ratio and air-liquid reaction time were analyzed according to the experimental data.It is found that the dehumidification efficiency of this system is 18.1%~26.9% under 9 groups of experimental conditions;the efficiency decreases when the salt quality concentration decreases from 38% to 35%;the liquid-air ratio greatly affects the dehumidification efficiency,which increases 50% when the liquid-air ratio increases from 0.18 to 0.84;increasing the reaction time helps improve the efficiency.Moreover,the temperature of the processed air is raised when the efficiency increases.