Ammonia Absorption Performance of a Liquid Desiccant Dehumidification System Applied in Laboratory Rodent Room

Shaojie Li,Xiaohua Liu,Tao Zhang
DOI: https://doi.org/10.1016/j.applthermaleng.2021.117523
IF: 6.4
2021-01-01
Applied Thermal Engineering
Abstract:Laboratory rodent room usually adopts full fresh air system with large ventilation rates and causes energy waste for heat-cold offset process. Liquid desiccant system is identified as an energy saving approach in humidity control field. This paper presents the ammonia absorption performance of a liquid desiccant dehumidification system applied in laboratory rodent room while considering air dehumidification requirements. Prior to the simulation process of the system, Henry's law constant (HC) of ammonia, one method to assess the solubility, in LiBr, LiCl, and CaCl2 solutions are tested at the salt concentration range of 20-50 wt% and at the temperature range of 10-50 degrees C. The ammonia concentration of supply air (Csa) in the LiBr condition is apparently smaller than that in LiCl and CaCl2 conditions of a liquid desiccant dehumidification system. In addition, Csa apparently increases with the increasing number of mass transfer units of ammonia (NTUa) and solution flow rate. The simulation results show that most ammonia is introduced by heat recovery process. An improved system structure is proposed to reduce ammonia transfer. Using the proposed heat recovery method, Csa is decreased by more than 70% over the initial system.