Experimental study on data center heat pipe air conditioning system

QIAN Xiao-Dong,Zhen Li,LI Zhi-Xin
2012-01-01
Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics
Abstract:According to the environmental characteristics of data center, R22 and R134a were chosen as the working fluids in the experiments to study the heat transfer performance and the optimal liquid filled ratio of the data center heat pipe air conditioning system. The experimental results indicate that data center heat pipe air conditioning system has the features of small working temperature difference and high refrigeration energy efficiency. With the increment of heat load, the temperature difference of cooling becomes larger. Comparison experiments show that the average heat transfer capability of the system filled with R22 is 19.2% higher than that with R134a as the working fluid, and the optimal liquid filled ratio are both about 80%. By measuring and analyzing the temperature distribution of the heat pipe system, the reason for the decrease of heat transfer capability due to the too large/small liquid filled ratio is explained.