Localization and Identification of Transient Power Quality Disturbances Based on Generalized S-transform

Qi LIU,Luo-wei ZHOU,Wei-guo LU
DOI: https://doi.org/10.3969/j.issn.1674-3415.2012.07.011
2012-01-01
Abstract:S-transform has fixed time-frequency resolution, leading to poor results of localizing transient power quality disturbances. A new method to localize the disturbances is proposed based on generalized S-transform. The method detects mutation peak in the high frequency time-amplitude curve, in order to increase localization accuracy. At first, modulus time-frequency matrix is calculated by generalized S-transform, then the disturbances’ start-stop time is localized using the high frequency time-amplitude curve, and four identification features are extracted according to maximum frequency spectrum curve, fundamental frequency amplitude curve and the localization results. At last, automatic classification of disturbance signals is performed by use of a rule-based decision tree. Simulation results show that the proposed localization method is simple and intuitive, with high accuracy. The number of identification features is small and they are effective with good classification results.
What problem does this paper attempt to address?