Fast S Transform-Based Classification of Power Quality Disturbance
MAN Weishi,ZHANG Zhiyu,KANG Qing,MIAO Yongkang,XI Xiaoli
DOI: https://doi.org/10.7652/xjtuxb201308023
2013-01-01
Abstract:Focusing on higher computation cost and lack of real-time detection for all techniques based on traditional S-transform to identify power quality disturbances,a real-time approach combining fast S-transform with least squares support vector machine is proposed.The standard deviation of module coefficients,maximum module coefficient of each frequency band,and module coefficient corresponding to the rated frequency are extracted from the one-dimensional vector of the fast S-transform of the original power quality signals as features,and the least squares support vector machine based on optimized parameters and the minimum output coding is used to classify and identify the voltage swell,voltage sag,voltage interruption,spike,transient oscillation and harmonic waves.Compared with the traditional approach based on S-transform,the proposed approach reduces the tasks in both extracting features and training of the support vector machine classifier due to fewer training samples.The longer the duration of the voltage disturbance signal,the higher the saving efficiency.To the same accuracy,for the disturbance signal with a length of 1 024 points,processing time can be saved by 99%.The classification accuracy of this approach gets up to 98% with higher anti-interference ability.