Classification of Short Duration Power Quality Disturbance Using S-Transform and Scale Zooming Standardization

赵俊,杨洪耕,李伟
DOI: https://doi.org/10.3969/j.issn.1674-0629.2010.03.015
2010-01-01
Abstract:A classification method for short duration power quality disturbance by adopting S-transform and scale zooming standardization was proposed.First,power quality disturbance signals were decomposed with S-transform time-frequency analysis.Then,the best scale was selected by using least square method.All types of the disturbance characteristics with different duration as well as amplitude were standardized by scale zooming.Finally,the only standard templates with unified time scale and bandwidth resolution were constructed which could be used to directly identify the type of disturbance by template matching.The proposed method is able to achieve the different length of disturbance classification without any artificial intelligence classifier,so it is simple and clear.The results of Matlab simulation and actual examples show that the method has a thick skin to noise and is effective to classify disturbance signals.
What problem does this paper attempt to address?