Numerical Simulation of Tail Water Discharge Test Model for River Water Source Heat Pump System

QING Xiao-xia,ZHANG Jing-yao,ZHOU Jian,YU Ling-ling
2012-01-01
Journal of Central South University
Abstract:In order to investigate the temperature distribution regulation of thermal discharge of river water source heat pump system,the flow control equation was set up and finite volume method of Fluent software was used,and the temperature of tail water discharge physical test model for river water source heat pump system was simulated numerically.The results show that the discharged tail water mainly influences on upper water at discharge outlet of river,and has little influence on middle water,and almost does nothing on bottom water.Water temperature is reduced gradually from discharge outlet to lower river,from upper layer to bottom layer.The absolutely relative error between the actual test temperatures by the physical test model and the numerical simulation results are within 1.73%, which means these two kinds of results have good agreement.