Research on Action Sensitivity of Discharge Counter for Surge Arrester

CUI Long-yue,GUO Jie,YU Yong
DOI: https://doi.org/10.16188/j.isa.1003-8337.2011.06.015
2011-01-01
Abstract:In the operation,discharge counter determine whether the action of surge arrester and record the number of surge arrester's actions,these can accumulate information and help to the field accident analysis;it is an important equipment for surge arrester.In actual operation,since the different of operating currents for the counters,resulting in inaccurate data recording,it not only makes the over-voltage analysis and the assessment of the state arrester operation become difficulty.It is important to study the sensitivity of the discharge counter for analyzing over-voltage and determining the surge arrester working condition.After studying the action sensitivity of discharge counter for 110 kV and below surge arrester,the result showed that the action sensitivity of discharge counter is related to the impulse current amplitude and waveform,and largely independent of current polarity.The discharge counter has obvious upper and lower limit current amplitude,the amplitude is related to the wave of impulse current,the shorter front time of the impulse current,the higher of the discharge counter's upper limit current amplitude.
What problem does this paper attempt to address?