Analysis of the Defects of Power Equipment in the 2008 Snow Disaster N Southern China Area

HOU Hui,YIN Xiang-gen,YOU Da-hai,CHEN Qing-qian,TONG Guang-yi,ZHENG Yi,SHAO De-jun
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.03.019
2009-01-01
Abstract:The extreme weather which happened in January 2008 in southern China caused thousands of power transmission line to be damaged in large area including the 500 kV main power grids. Thousand of electric power steel towers and poles were collapsed and even caused several people injury and death. We analyzed the reasons why so many lines, towers and poles were broken or collapsed and their existing problems according to the large area blackout disaster. The main problems were: being not strong enough to conform to the national design standards of the transmission line and tower, aging of devices, to use new technologies for preventing disaster, and to avoid using same type of equipment at same area, etc. The secondary equipment injuries are mainly due to communication devices' damage that affect the SCADA system and some protection devices that were relied on communication channel such as differential protection. And the security and stabilizing control equipment are also briefly analyzed. Finally, some improved measures and suggestions are put forward according to the above problems.