Application of Infrared Temperature Measurement Technology in Fault Diagnosis of Zinc Oxide Arresters

DA Feng,WANG Gang,ZHU Ya-fei,ZHANG Gai-jie,WU Xiao-wen
DOI: https://doi.org/10.3969/j.issn.1673-7598.2012.12.019
2012-01-01
Abstract:Heat is one of the most typical phenomena of malfunctioning power apparatus.The infrared temperature measurement technology can be used to diagnose the early defects of the equipments in substations.Recently,the technology was widely applied in Xiaogan Power Supply Company for condition-based maintenance of the power apparatus,and it was proved to be effective because lots of serious equipment defects had been found.The detailed measure dealing with one of the defects,that the 220 kV metal oxide arresters(MOA) was found to be abnormal from Infrared temperature measurement,was introduced in this paper.The live detection, off-line experiment and disassembling inspection on the MOA showed that the infrared temperature measurement technologv and ohmic current measurement could be used to detect the moistening defect of the MOA instantly and accurately.This will improve the reliability of the MOA in operation.