Lightning Protection Study of Transmission Line,Part Ⅰ:Lightning Parameters

CHEN Shui-ming,HE Jin-liang,ZENG Rong
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.12.005
2009-01-01
Abstract:Obtaining actual lightning parameters is the fundament of lightning protection of transmission lines.Based on the comprehensive analysis on the methods to acquire lightning parameters,we analyzed the current research states and existed problems of lightning parameters,including annual lightning day,ground flash density,magnitude and waveform of lightning current.The lightning activities have obvious topographical feature,presently the lightning location system(LLS) should be fully applied to acquire the annual lightning day,ground flash density,magnitude of lightning current in different areas.Moreover,the monitoring devices of lightning current should be installed on typical transmission towers with different voltage grades in different areas to obtain the characteristics of real lightning current waveforms and magnitudes,and calibrate and check the lightning current magnitudes obtained from LLS.All these would make the lightning protection of power system focusing on the actual targets.Four sets of the developed monitoring devices of lightning current were installed,and the first lightning current waveform in China,which was similar to the standard waveform recommended by CIGRE,was recorded.