India blackout and three functions of protective relay

DONG Xin-zhou,CAO Run-bin,WANG Bin,SHI Shen-xing,Dominik Bak
2013-01-01
Abstract:On July 30 and 31,2012,India experienced two electric power blackouts.These two blackouts were both triggered by tripping of zone-3 distance relay of the same transmission line due to overload,and caused unreasonable action of other relays which resulted in cascading trip and led to widespread power blackouts.India's blackouts have exposed the vulnerability of the existing power system,especially the defects of protective relay in case of overload and power swing.Based on the analysis of relay actions in the blackouts,this paper proposes three functions of protective relay to meet the security demand of modern power grid,which are system protection function for security of power system,preventive protection function and the function of rapid removal of fault equipment.
What problem does this paper attempt to address?