Automatic control of precooling process in EAST cryogenic system based on DCS

Zhou Zhiwei,Xia Genhai,Zhuang Ming,Zhang Qiyong,Hu Liangbing
DOI: https://doi.org/10.3969/j.issn.1000-6516.2011.02.008
IF: 2.134
2011-01-01
Cryogenics
Abstract:In order to avoid the destruction of heat stress on EAST Tokamak,the cool-down temperature differences of the superconducting magnets and thermal shields during 300-80 K precooling process should be rigorously controlled.Meanwhile,the cryogenic system is required to supply proper mass flow and pressure drop to ensure every cold-mass components cooled-down fast and synchronously.Via analysis of cryogenic control flow,the control loops and requirements were decided,the precooling operation mode as well as its sequence control flow was also designed.Aiming at the coupling control of temperature difference and pressure drop,a grading decoupling control scheme was presented.The control strategy was realized on DCS.Tested by two experiments,the decoupling control was stable and fast-synchronous cool down was realized.The automatic control substituted manual precooling operation lasting over ten days,so the automation degree of the system was highly promoted.
What problem does this paper attempt to address?