Numerical analysis and experiment of frosting quality of finned-tube evaporators in low temperature condition

Wu Jinyu,Chen Jiangping
DOI: https://doi.org/10.3969/j.issn.1000-6516.2008.01.007
IF: 2.134
2008-01-01
Cryogenics
Abstract:Frosting of evaporator was researched based on CFD simulation and test.The correctional species transport and finite-rate reaction model to simulate the frosting of evaporator was put forward.With substitued latent heat of sublimation for activation energy of chemical reactions,the physical reaction H2O(g) H2O(s) was changed into chemical reaction.In low temperature condition(blow-20 ℃),the quantity of evaporator frosting was studied when the inlet velocity of humid air was 2.0 m/s,1.2 m/s,0.8 m/s and the relative humidity was 60%,80% respectively.The results show that the quantity of frost increases with the inlet velocity and the relative humidity and the numerical simulation results accord with the test results very well.
What problem does this paper attempt to address?