Study on Biological Stability of Water in Water Distribution System in a Northern City

ZHANG Xin-yu,LI Xiu-jie,LI Xin,WANG Liang-liang,QI Jing-yao,YUAN Yi-xing
DOI: https://doi.org/10.3321/j.issn:1000-4602.2008.19.026
2008-01-01
Abstract:The indexes AOC and BDOC were used to evaluate the biological stability of water in water distribution system in a northeast city of China.The results show that the concentrations of AOC and BDOC are 39 to 379 μg/L and 0.8 to 2.8 mg/L in water which is biologically unstable.The concentrations of AOC and BDOC generally decline with the prolongation of water distribution system.The residual chlorine has heavy influence on AOC and BDOC.The ratio of AOC in BDOC is 5.8% and 6.2% respectively in winter and summer.