THE COMPARISON OF IMPACT OF THE AIRFLOWS OF AN AXIAL FAN'S SUCTION AND BLOWING SECTIONS ON HUMAN SENSATION

Hongjun Li,Xiaochun Chen,Yingxin Zhu
2007-01-01
Abstract:As two common kinds of air supply modes, natural wind and mechanical wind have obvious differences on human sensation. From former researches, it can be seen that the 1/f fluctuation property of the spectrum of natural wind is an important factor to cause people feel more comfortable. While, the spectrum of mechanical wind often deviates from 1/f fluctuation because of its relatively more high-frequency fluctuating energy, which also brings some difficulties for imitating natural wind. This paper compares the airflow of the suction section with that of the blowing section of an axial fan. The result shows that high-frequency fluctuating energy of the suction section's airflow is lower than that of the blowing section's, consequently the spectrum of the suction section's airflow is relatively more close to 1/f fluctuation. By using these two airflows to blow the subjects' arms, the subject's sensation vote was conducted. Majority of the subjects reflected that the blowing section's airflow was harder and with more violent stimulus than the suction section's, and the suction section's airflow was more acceptable to the subjects. The experiment finds a simple way to decrease high-frequency fluctuating energy of mechanical airflow, which will be helpful for imitating natural wind better.
What problem does this paper attempt to address?