Airflow Pattern Induced by Ceiling Fan under Different Rotation Speeds and Blowing Directions

Huan Wang,Maohui Luo,Guijin Wang,Xianting Li
DOI: https://doi.org/10.1177/1420326x19890054
2019-01-01
Abstract:Ceiling fans have been widely used as effective cooling and air mixing method for building environment conditioning. Understanding its airflow characteristics can be helpful to utilize ceiling fan or integrate it with background air conditioning system. However, the airflow induced by ceiling fan has different flow patterns under different rotating speeds and blowing directions. To date, it is still challenging to capture those complicated airflow fields in room scale. In this study, the airflow pattern induced by a ceiling fan was measured with a new technology, quad-view colour sequence particle streak velocimetry. A series of isothermal experiments were conducted under five rotation speed levels with downward and upward blowing directions in a room-size (4 m × 2.5 m × 3 m) chamber. Based on comprehensive three-dimensional three-component vector measurement results, the average velocity, turbulence intensity and vorticity on the middle section were calculated and used to analyse airflow patterns induced by ceiling fan. The results show that the blowing direction of the fan determines the indoor airflow pattern. When blowing downward, the flow will cause high diversion between jet core under the fan blades and surrounding region. While for upward blowing, the air speed in lower part of the room is much lower but pretty uniform. The detailed measured airflow fields can serve as reference for ceiling fan design and operation.
What problem does this paper attempt to address?