The AC Side Output Filter Design of Shunt Active Power Filter

JU Jian-yong,CHEN Min,XU Jun,XU De-hong
DOI: https://doi.org/10.3969/j.issn.1007-449x.2010.10.003
2010-01-01
Abstract:In order to resolve the problems of grid side current distortion amplification and damping resistance heating,an engineering design method of active power filter ac side output filter was proposed.Second order high-pass filter was selected as the topology of active power filter output filter.This paper discussed the design method of output filter based on comprehensive consideration of switching ripple current filtering,total harmonic distortion(THD),var of capacitor,power loss of output filter through theoretical analysis and simulation.The proposed method was used to design an output filter for a 50 kVA shunt active power filter.The results show that current ripple remains 1/4 of that before filtering,grid current THD rises about a point and damping resistor heating is controlled effectively through bypassing more than 90% frequency current.The results prove the validity of the proposed method.
What problem does this paper attempt to address?