Improved Method of Detecting Harmonic Currents Based on Instantaneous Reactive Power Theory
Li CHENG,Mu-hong FAN,Zhen-yu WANG,Xing YIN,Xing-qiao LIU,Jun ZHU
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.04.012
2007-01-01
Abstract:Quickly and accurately detecting the harmonic currents is the precondition to improve the electricity supply and to ensure the normal operation of the power system. In order to improve real-time reactive power compensation and quick-response characteristics of conventional active power filter(APF) at present,this paper proposed a kind of improved ip,iq detecting method, which is based on instantaneous reactive power theory. By means of building a kind of detecting circuit model and analyzing the model,this method,applied in APF,simply replaced the conventional lower-pass filter(LPF) with 2 integrals,2 time-delay circuits and 2 amplifiers,thus reducing the delay-time from one cycle to 1/6 cycle. Meanwhile,the model could also be applied to a single-phase circuit,three-phase four-wire circuit and three-phase unbalanced load system. For example,when applied to a single-phase circuit,its total detecting delay-time within a supply period was only 5T/6. With the MATLAB simulation results,it has been proved that this method can quickly and accurately detect the harmonic and reactive power currents in the power system with symmetry and distortion voltage or with symmetry and no distortion voltage,and that it can track the harmonic currents,and that the total delay-time of the method within a period even can be reduced from 0.02 second to 0.0033 second. So this method can meet the real-time detecting demand in the power system.