Detection Method of Unified Power Quality Conditioner Based on Park Transformation

MEI Hui-nan,ZHU Zhong-hua,CHENG Shi-jie
DOI: https://doi.org/10.3969/j.issn.1672-0792.2005.01.005
2005-01-01
Abstract:The Unified Power Quality Conditioner is a kind of compositive compensation equipment combining the series active power filter and parallel active filter. This paper introduces its function and system configuration, and analyzes the difference of detecting method between UPQC and alone active power filters. This paper also presents an improved detecting method based on instantaneous reactive power theory. In this method, by using Park transformation, the peak amplitude and phase of positive basic frequency voltage are detected separately from unbalanced and distorted voltage in the series portion of UPQC, and the current reference of parallel portion of UPQC is determined by the detection of series portion and the theory of power balance. Compared with the existing detection method of UPQC, the proposed method avoids complex phasor calculation, and it does not need phase-locked loop and filter for three-phase unbalanced or distorted voltages. The simulation verifies the correctness of the method.
What problem does this paper attempt to address?